78 HB700 | CPU | PMC921xEx | en | 24-04
Hardware description
iC9200 Series
Technical data > iC9212M-FSoE - PMC9212ES
Order no. PMC9212ES
SliceBus
Amount of process data per module up to 60 bytes
Max number of modules 64
Cycle time [ms] 500 µs .. 512 ms
OPC UA
OPC UA
ü
Server
ü
Max parallel sessions 5
Sampling rates 100 ms .. 5 s
Encryption suite Basic128Rsa15
ü
Encryption suite Basic256
ü
Encryption suite Basic256Sha256
ü
Encryption suite Aes256Sha256RsaPss
ü
Encryption suite Aes128Sha256RsaOaep
ü
Programming
IEC 61131-3
ü
Web Based Management (WBM)
Web Based Management (WBM)
ü
Ethernet
Ethernet-capable ports X3/X4: 2 Ports x 10/100 Mbit/s (Half/Full duplex)
EtherCAT Master
Number of EtherCAT-slaves 512
Update time 500 µs .. 512 ms
EoE support -
CoE support
ü
FoE support -
Distributed Clock support
ü
Hotconnect Slaves
ü
Isochronous mode
ü
Functional safety
Minimum time 5 ms
Maximum time 15 ms
Program memory safe program 64 KB
Data memory 16 KB
Safety protocol FSoE
Number of FSoE devices 32

Table of Contents

Other manuals for YASKAWA iC9200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA iC9200 Series and is the answer not in the manual?

YASKAWA iC9200 Series Specifications

General IconGeneral
BrandYASKAWA
ModeliC9200 Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals