1.6 F: Option Settings
134 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
■ F6-51: DeviceNet Communication Speed
Sets the communication speed for a DeviceNet option card if installed.
Settings:
■
F6-52: DeviceNet PCA Setting
Defines the data format for data the drive receives from the DeviceNet master.
■ F6-53: DeviceNet PPA Setting
Defines the data format for data sent from the drive to the DeviceNet master.
■ F6-54: DeviceNet Idle Mode Fault Detection
Determines if the drive detects an EF0 fault, e.g. when no data are receive from the master
(e.g., when the master is in idle mode).
No. Parameter Name Setting Range Default
F6-50 <1>
<1> Valid from drive firmware version 1011 and later. Parameter number was F6-20 in older software.
DeviceNet MAC Address 0 to 63 0
No. Parameter Name Setting Range Default
F6-51 <1>
<1> Valid from drive firmware version 1011 and later. Parameter number was F6-21 in older software
DeviceNet Communication Speed 0 to 4 3
F6-51 Communication Speed F6-51 Communication Speed
0 125 kbps 3 Adjustable from Network
1 250 kbps 4 Auto detection
2
500 kbps
No. Parameter Name Setting Range Default
F6-52 <1>
<1> Valid from drive firmware version 1011 and later. Parameter number was F6-22 in older software.
DeviceNet PCA Setting 0 to 255 0
No. Parameter Name Setting Range Default
F6-53 <1>
<1> Valid from drive firmware version 1011 and later. Parameter number was F6-23 in older software.
DeviceNet PPA Setting 0 to 255 0