1.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 135
Parameter Details
1
Setting 0: Disabled, No Fault Detection
Setting 1: Enabled
F6-56 to F6-61: DeviceNet Scaling Factors
These parameters define scaling factors for drive monitors in the DeviceNet Class ID 2AH -
AC/DC Drive Object.
Setting
The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value x 2
Scaling
Example:
If the drive output frequency monitor (U1-02) is 50.0 and the scaling is set to F6-56 = 6, then
the value in the AC/DC Drive Object 2AH, Instance 1, Attribute 7 would be 500 x 2
6
=
32000.
F6-62: DeviceNet Heartbeat Interval
Sets the heartbeat interval for DeviceNet communications. A setting of 0 disables the
Heartbeat function.
No. Parameter Name Setting Range Default
F6-54 <1>
<1> Valid from drive firmware version 1011 and later. Parameter number was F6-24 in older software.
DeviceNet Idle Mode Fault Detection 0 or 1 0
No. Parameter Name Setting Range Default
F6-56 <1>
<1> Valid from drive firmware version 1011 and later.
DeviceNet Speed Scaling -15 to 15 0
F6-57 <1> DeviceNet Current Scaling -15 to 15 0
F6-58 <1> DeviceNet Torque Scaling -15 to 15 0
F6-59 <1> DeviceNet Power Scaling -15 to 15 0
F6-60 <1> DeviceNet Voltage Scaling -15 to 15 0
F6-61 <1> DeviceNet Time Scaling -15 to 15 0
No. Parameter Name Setting Range Default
F6-56 <1>
<1> Valid from drive firmware version 1011 and later.
DeviceNet Heartbeat 0 to 10 0