1.6 F: Option Settings
136 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
F7-01 to F7-04: Ethernet IP Address 1 to 4
The combination of these parameters sets the IP address of an Ethernet option board if
installed. The address is set like F7-01.F7-02.F7-03.F7-04. The default address is
192.168.1.20.
F7-05 to F7-08: Ethernet Subnet Mask 1 to 4
The combination of these parameters sets the Subnet Mask of an Ethernet option board if
installed. The mask is set like F7-05.F7-06.F7-07.F7-08. The default setting is
255.255.255.0.
F7-09 to F7-12: Ethernet Gateway Address 1 to 4
The combination of these parameters sets the gateway address of an Ethernet option board if
installed. The address is set as F7-09.F7-10.F7-11.F7-12. The default address is 192.168.1.1.
No. Parameter Name Setting Range Default
F7-01
<1> Valid from drive firmware version 1011 and later.
Ethernet IP Address 1 0 to 255 192 <1>
F7-02 Ethernet IP Address 2 0 to 255 168 <1>
F7-03 Ethernet IP Address 3 0 to 255 1 <1>
F7-04 Ethernet IP Address 4 0 to 255 20 <1>
No. Parameter Name Setting Range Default
F7-05
<1> Valid from drive firmware version 1011 and later.
Subnet Mask 1 0 to 255 255 <1>
F7-06 Subnet Mask 2 0 to 255 255 <1>
F7-07 Subnet Mask 3 0 to 255 255 <1>
F7-08 Subnet Mask 4 0 to 255 0
No. Parameter Name Setting Range Default
F7-09
<1> Valid from drive firmware version 1011 and later.
Gateway Address 1 0 to 255 192<1>
F7-10 Gateway Address 2 0 to 255 168 <1>
F7-11 Gateway Address 3 0 to 255 1 <1>
F7-12 Gateway Address 4 0 to 255 1 <1>