1.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 137
Parameter Details
1
■ F7-13: Ethernet Address Mode at Startup
Determines how the Ethernet option card IP address is set.
Setting 0: User Defined Setting
Setting 1: BOOTP
Setting 2: DHCP
■
F7-14: Ethernet Duplex Mode Selection
Sets the duplex mode for Ethernet communications.
Setting 0: Auto Negotiate
Setting 1: Half Duplex Forced
Setting 2: Full Duplex Forced
■
F7-15: Ethernet Communication Speed Selection
Sets the duplex mode for Ethernet communications.
Setting 0: Auto Detection
Setting 10: 10 Mbps
Setting 100: 100 Mbps
■
F7-16: Ethernet Communication Loss Time Out
Sets the communication loss time out value.
No. Parameter Name Setting Range Default
F7-13 Address Mode at Startup 0 to 2 0
No. Parameter Name Setting Range Default
F7-14 <1>
<1> Valid from drive firmware version 1011 and later. Parameter number was F7-15 in older software.
Duplex Mode Selection 0 to 2 0
No. Parameter Name Setting Range Default
F7-15 <1>
<1> Valid from drive firmware version 1011 and later. Parameter number was F7-18 in older software.
Communication Speed Selection 0, 10, 100 0
No. Parameter Name Setting Range Default
F7-16 <1> Communication Loss Time Out 0 to 300 0