9 Fully-closed Loop Control
9.1.6 Precautions When Using an External Incremental Encoder by Magnescale
9-12
4
Perform a program JOG opera-
tion.
Items to Check
Does the fully-closed loop
control operate correctly when
operating the SERVOPACK in
standalone mode?
Perform a program JOG operation
and check that the distance that the
servomotor moved is the same as
the distance that is set in Pn531.
Note: Start from a low speed and
gradually increase the speed.
Program JOG related param-
eters (Pn530 to Pn536)
SERVOPACK
5
Operate the SERVOPACK and
converter.
Items to Check
Does the fully-closed loop
control operate correctly
including the host controller?
Input the position reference and
check that the SERVOPACK and
converter operate correctly.
Note: Start from a low speed and
gradually increase the speed.
Host controller
(cont’d)
Procedure Description Operation
Parameters Requiring
Settings
Controller