No. Name Description
o1-03
Digital Operator Display
Selection
0: Hz
1: % (100% = E1-04)
2: r/min (enter the number of motor poles into E2-04/E4-04/E5-04)
3: User defined by parameters o1-10 and o1-11
o1-10
Frequency Reference Setting and
User-Set Display
Refer to V1000 Technical Manual for details.
o1-11
Frequency Reference Setting /
Decimal Display
o2: Multi-Function Selections
Use o2 parameters to configure LED digital operator key functions.
o2-01 LO/RE Key Function Selection Refer to V1000 Technical Manual for details.
o2-02 STOP Key Function Selection
Enables/Disables the operator panel STOP key when the drive is
operated form external sources (not operator).
0: Disabled.
1: Enabled
o2-03 User Parameter Default Value Refer to V1000 Technical Manual for details.
o2-04 Drive Model Selection Refer to V1000 Technical Manual for details.
o2-05
Frequency Reference Setting
Method Selection
0: Data/Enter key must be pressed to enter a frequency reference.
1: Data/Enter key is not required. The frequency reference is adjusted
by the “up” and “down” arrow keys.
o2-06
Operation Selection when Digital
Operator is Disconnected
0: The drive will continue operation
1: The drive will trigger a fault (oPr) and the motor will coast to stop
o2-07
Motor Direction at Power Up when
Using Operator
Refer to V1000 Technical Manual for details.
o2-09 Factory use
o3: Copy Function
Use o3 parameters to Read, Copy and Verify the parameter settings to and from the drive.
o3-01 Copy Function Selection Refer to V1000 Technical Manual for details.
o3-02 Copy Allowed Selection Refer to V1000 Technical Manual for details.
o4: Maintenance Period
Use o4 parameters to perform maintenance.
o4-01
Accumulated Operation Time
Setting
Sets the starting value for the cumulative operation time of the drive in
units of 10 h.
o4-02
Accumulated Operation Time
Selection
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation
time).
o4-03
Cooling Fan Operation Time
Setting
Refer to V1000 Technical Manual for details.
o4-05 Capacitor Maintenance Setting Refer to V1000 Technical Manual for details.
o4-07
Soft Charge Bypass Relay
Maintenance Setting
Refer to V1000 Technical Manual for details.
o4-09 IGBT Maintenance Setting Refer to V1000 Technical Manual for details.
B.1 Parameter Table
196
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide