9-19
IM 04P01B01-01E
Operations Related to the Computation Function (/M1 Option)
9
9.11 Setting the Alarm Delay Duration
This section explains the details of setting the duration of the delay high limit and delay
low limit alarms.
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Press the key or SHIFT + key to select Math and then press the key.
3.
Press the key or SHIFT + key to select Aux and then press the key.
4.
Press the key or SHIFT + key to select Alm delay T and then press the
key.
5.
Set each item and press the key.
Use the
key or SHIFT + key to select values.
For the procedure on how to enter values or characters, see section 4.2.
If you press the ESC key in the middle of the operation, the settings entered up to
then are cancelled, and the display returns to a higher level menu.
6.
When the Setting complete screen appears, do either of the following:
Press the
key to set other channels.
If you are done, press the ESC key.
7.
Hold down the
MENU
key for 3 seconds to return to Operation mode.
Set the channel range.
The new setting takes effect.
ESC/?
Set the alarm delay time.
First channel Last channel
Math=Aux
Aux=Alm delay T
Duration= 10
CH=0A-0A
0A-0A Channel
Explanation
Duration
The duration can be set to a value in the range of 1 to 3600 s.
However, if the scan interval on the dot model is 2.5 s, the actual duration is an integer
multiple of 2.5 s. If the set value is not equal to an integer multiple of 2.5 s, the duration is
the smallest integer multiple of 2.5 s greater than the set value.
Example: The actual duration for 1 s and 2 s is 2.5 s.
<Related Topics> Enabling the alarm delay function: Section 7.15