10-1
IM 05P03D21-01EN
Retransmission Output Functions
10
10.1 SettingRetransmissionOutputTerminal,Type,
andScales
Description
► Currentoutputrange:10.3ChangingCurrentOutputRange
20 mA (output signal)
0.0
°C
200.0
°C
4 mA
50.0
°C
150.0
°C
Retransmission scale
PV scale
Output range
Minimum value of
PV input range
Maximum value of
PV input range
To Recorder
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
RTS
Retransmission
out type of
RET
EASY
OFF: Disable
PV1: PV
LPS: 15 V DC loop power supply
OUT
RTH
Maximum
value of
retransmission
output scale of
RET
STD
When RTS = PV1
RTL + 1 digit to 30000
-19999 to RTH - 1 digit
Decimal point position:
When RTS=PV1 decimal point
position is same as that of PV
input.
RTL
Minimum
value of
retransmission
output scale of
RET
STD
Parameters and Corresponding Terminals
RTS, RTH, RTL RET terminal
Chapter 10 Retransmission Output Functions

Table of Contents

Other manuals for YOKOGAWA UM33A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UM33A and is the answer not in the manual?

YOKOGAWA UM33A Specifications

General IconGeneral
BrandYOKOGAWA
ModelUM33A
CategoryTouch Panel
LanguageEnglish

Related product manuals