Alarm Functions
9
9.2 SettingNumberofAlarmGroupstoUse
Description
Up to eight alarm groups of alarm type, alarm hysteresis, alarm (On-/Off-) delay timer,
and alarm setpoint are available.
Unused alarm parameters can be hidden and their functions can be turned off.
When ALNO. = 4, for example, only the four groups of alarm type, PV velocity alarm time
setpoint, alarm hysteresis, alarm delay timer, and alarm setpoint are displayed.
If the number of alarms is set to zero, alarm setpoint parameters, alarm type parameters,
and menu are not displayed.
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
ALNO.
Number of alarm
groups
PRO 0 to 8 CTL