90 ACS550 User’s Manual
Parameters
Group 22: ACCEL/DECEL
2201
ACC/DEC 1/2 SEL -6…7 1 5 (DI5)
2202
ACCELER TIME 1 0.0…1800.0 s 0.1 s 5.0 s
2203
DECELER TIME 1 0.0…1800.0 s 0.1 s 5.0 s
2204
RAMP SHAPE 1 0.0 = LINEAR, 0.1…1000.0 s 0.1 s 0.0 s
2205
ACCELER TIME 2 0.0…1800.0 s 0.1 s 60.0 s
2206
DECELER TIME 2 0.0…1800.0 s 0.1 s 60.0 s
2207
RAMP SHAPE 2 0.0 = LINEAR, 0.1…1000.0 s 0.1 s 0.0 s
2208
EMERG DEC TIME 0.0…1800.0 s 0.1 s 1.0 s
2209
RAMP INPUT 0 -6…7 1 0 (NOT SEL)
Group 23: SPEED CONTROL
2301
PROP GAIN 0.00…200.00 0.01 10.00
2302
INTEGRATION TIME 0.00…600.00 s 0.01 s 2.50 s
2303
DERIVATION TIME 0…10000 ms 1 ms 0 ms
2304
ACC COMPENSATION 0.00…600.00 s 0.01 s 0.00 s
2305
AUTOTUNE RUN 0 = OFF, 1 = ON 10 (OFF)
Group 24: TORQUE CONTROL
2401
TORQ RAMP UP 0.00…120.00 s 0.01 s 0.00 s
2402
TORQ RAMP DOWN 0.00…120.00 s 0.01 s 0.00 s
Group 25: CRITICAL SPEEDS
2501
CRIT SPEED SEL 0=OFF, 1 = ON 10 (OFF)
2502
CRIT SPEED 1 LO 0…30000 rpm / 0.0…500.0 Hz 1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
2503
CRIT SPEED 1 HI 0…30000 rpm / 0.0…500.0 Hz 1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
2504
CRIT SPEED 2 LO 0…30000 rpm / 0.0…500.0 Hz 1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
2505
CRIT SPEED 2 HI 0…30000 rpm / 0.0…500.0 Hz 1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
2506
CRIT SPEED 3 LO 0…30000 rpm / 0.0…500.0 Hz 1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
2507
CRIT SPEED 3 HI 0…30000 rpm / 0.0…500.0 Hz 1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
Group 26: MOTOR CONTROL
2601
FLUX OPT ENABLE 0 = OFF, 1 = ON 10 (OFF)
2602
FLUX BRAKING 0 = OFF, 1 = ON 10 (OFF)
2603
IR COMP VOLT 0.0…100.0 V 0.1 V Size dependent
2604
IR COMP FREQ 0…100% 1% 80%
2605
U/F RATIO 1 = LINEAR, 2 = SQUARED 11 (LINEAR)
2606
SWITCHING FREQ 1, 4, 8, 12 kHz - 4 kHz
2607
SWITCH FREQ CTRL 0 = OFF, 1 = ON 11 (ON)
2608
SLIP COMP RATIO 0…200% 1% 0
2609
NOISE SMOOTHING 0 = DISABLE, 1 = ENABLE 10 (DISABLE)
2619
DC STABILIZER 0 = DISABLE, 1 = ENABLE 10 (DISABLE)
Group 29: MAINTENANCE TRIG
2901
COOLING FAN TRIG 0.0…6553.5 kh, 0.0 disables 0.1 kh 0.0 kh
2902
COOLING FAN ACT 0.0…6553.5 kh 0.1 kh 0.0 kh
2903
REVOLUTION TRIG 0…65535 Mrev, 0 disables 1 Mrev 0 Mrev
2904
REVOLUTION ACT 0…65535 Mrev 1 Mrev 0 Mrev
2905
RUN TIME TRIG 0.0…6553.5 kh, 0.0 disables 0.1 kh 0.0 kh
2906
RUN TIME ACT 0.0…6553.5 kh 0.1 kh 0.0 kh
Code Name Range Resolution Default User S