154 Parameters
01.30 Nominal torque
scale
Torque that corresponds to 100% of nominal motor torque.
The unit is selected by parameter 96.16 Unit selection
Note: This value is copied from parameter 99.12 Motor
nominal torque if entered. Otherwise the value is calculated
from other motor data.
-
0.000… N·m or lb·ft Nominal torque. 1 = 1 unit
01.31 Ambient
temperature
Measured temperature of incoming cooling air. The unit is
selected by parameter 96.16 Unit selection.
-
-40 … 120 °C or °F Cooling air temperature. 1 = 1°
01.32 Inverter GWh
regenerating
Amount of energy that has passed through the drive (towards
the supply) in full gigawatt-hours. The minimum value is zero.
-
0…32767 GWh Regenerative energy in GWh. 1 = 1 GWh
01.33 Inverter MWh
regenerating
Amount of energy that has passed through the drive (towards
the supply) in full megawatt-hours. Whenever the counter
rolls over, 01.32 Inverter GWh regenerating is
incremented.The minimum value is zero.
-
0…999 MWh Regenerative energy in MWh. 1 = 1 MWh
01.34 Inverter kWh
regenerating
Amount of energy that has passed through the drive (towards
the supply) in full kilowatt-hours. Whenever the counter rolls
over, 01.33 Inverter MWh regenerating is incremented.The
minimum value is zero.
-
0…999 kWh Regenerative energy in kWh. 10 = 1 kWh
01.35 Mot - regen energy
GWh
Amount of net energy (motoring energy - regenerating
energy) that has passed through the drive in full gigawatt-
hours.
-
-32768…32767
GWh
Energy balance in GWh. 1 = 1 GWh
01.36 Mot - regen energy
MWh
Amount of net energy (motoring energy - regenerating
energy) that has passed through the drive in full megawatt-
hours. Whenever the counter rolls over, 01.35 Mot - regen
energy GWh is incremented or decremented.
-
-999…999 MWh Energy balance in MWh. 1 = 1 MWh
01.37 Mot - regen energy
kWh
Amount of energy (motoring energy - regenerating energy)
that has passed through the drive in full kilowatt-hours.
Whenever the counter rolls over, 01.36 Mot - regen energy
MWh is incremented or decremented.
-
-999…999 kWh Energy balance in kWh. 10 = 1 kWh
01.61 Abs motor speed
used
Absolute value of 01.01 Motor speed used.-
0.00 … 30000.00
rpm
Measured or estimated motor speed. See par.
46.01
01.62 Abs motor speed% Absolute value of 01.03 Motor speed %
.-
0.00 … 1000.00% Measured or estimated motor speed. 10 = 1%
01.63 Abs output
frequency
Absolute value of 01.06 Output frequency.-
0.00 … 500.00 Hz Estimated output frequency. See par.
46.02
01.64 Abs motor torque Absolute value of 01.10 Motor torque.-
0.0 … 1600.0% Motor torque. See par.
46.03
No. Name/Value Description Def/FbEq16