Parameters 155
01.65 Abs output power Absolute value of 01.14 Output power.-
0.00 … 32767.00
kW or hp
Output power. 1 = 1 unit
01.66 Abs output power %
motor nom
Absolute value of 01.15 Output power % of motor nom.-
0.00 … 300.00% Output power. 10 = 1%
01.68 Abs motor shaft
power
Absolute value of 01.17 Motor shaft power.-
0.00 … 32767.00
kW or hp
Motor shaft power. 1 = 1 unit
01.70 Ambient
temperature %
Measured temperature of incoming cooling air.
The amplitude range of 0…100% corresponds to 0…60 °C or
32…140 °F.
See also 01.31 Ambient temperature.
-
-200.00 … 200.00% Cooling air temperature. 100 = 1%
01.102 Line current (Only visible when IGBT supply unit control activated by
95.20)
Estimated line current flowing through the supply unit.
-
0.00 … 30000.00 A Estimated line current. See par.
46.05
01.104 Active current (Only visible when IGBT supply unit control activated by
95.20)
Estimated active current flowing through the supply unit.
-
0.00 … 30000.00 A Estimated active current. See par.
46.05
01.106 Reactive current (Only visible when IGBT supply unit control activated by
95.20)
Estimated reactive current flowing through the supply unit.
-
0.00 … 30000.00 A Estimated reactive current. See par.
46.05
01.108 Grid frequency (Only visible when IGBT supply unit control activated by
95.20)
Estimated frequency of the power supply network.
-
0.00 … 100.00 Hz Estimated supply frequency. See par.
46.02
01.109 Grid voltage (Only visible when IGBT supply unit control activated by
95.20)
Estimated voltage of the power supply network.
-
0.00 … 2000.00 V Estimated supply voltage. 10 = 1 V
01.110 Grid apparent
power
(Only visible when IGBT supply unit control activated by
95.20)
Estimated apparent power being transferred through the
supply unit.
-
-30000.00 …
30000.00 kVA
Estimated apparent power. See par.
46.04
01.112 Grid power (Only visible when IGBT supply unit control activated by
95.20)
Estimated power being transferred through the supply unit.
-
-30000.00 …
30000.00 kW
Estimated supply power. See par.
46.04
No. Name/Value Description
Def/FbEq16