Parameters 319
33.35 Edge counter 1
warn message
Selects the optional warning message for signal edge counter
1.
Edge counter
1 exceeded
Edge counter 1
exceeded
A888 Edge counter 1. The message text can be edited on the
control panel by choosing Menu – Settings – Edit texts.
2
Counted main
contactor
A884 Main contactor.11
Counted output
relay
A881 Output relay.12
Counted motor
starts
A882 Motor starts.13
Counted power ups A883 Power ups.14
Counted DC
charges
A885 DC charge.15
33.40 Edge counter 2
actual
Displays the actual present value of signal edge counter 2.
The counter is incremented every time the signal selected by
parameter 33.43 Edge counter 2 source switches on or off (or
either, depending on the setting of 33.42 Edge counter 2
function). A divisor may be applied to the count (see 33.44
Edge counter 2 divider).
When the counter exceeds the limit set by 33.41 Edge
counter 2 warn limit, bit 3 of 33.01 Counter status is set to 1.
The warning specified by 33.45 Edge counter 2 warn
message is also given if enabled by 33.42 Edge counter 2
function.
The counter can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
-
0…4294967295 Actual present value of signal edge counter 2. -
33.41 Edge counter 2
warn limit
Sets the warning limit for signal edge counter 2. 0
0…4294967295 Warning limit for signal edge counter 2. -