350 Parameters
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
Other [bit] Source selection (see Terms and abbreviations on page 148). -
40.43 Set 1 sleep level Defines the start limit for the sleep function when parameter
40.41 Set 1 sleep mode is set to Internal.
0.0
0.0 … 32767.0 Sleep start level. 1 = 1
40.44 Set 1 sleep delay Defines a delay before the sleep function actually becomes
enabled, to prevent nuisance sleeping.
The delay timer starts when the sleep condition selected by
parameter 40.41 Set 1 sleep mode becomes true, and resets
if the condition becomes false.
60.0 s
0.0 … 3600.0 s Sleep start delay. 1 = 1 s
40.45 Set 1 sleep boost
time
Defines a boost time for the sleep boost step. See parameter
40.46 Set 1 sleep boost step.
0.0 s
0.0 … 3600.0 s Sleep boost time. 1 = 1 s
40.46 Set 1 sleep boost
step
When the drive is entering sleep mode, the process setpoint
is increased by this value for the time defined by parameter
40.45 Set 1 sleep boost time.
If active, sleep boost is aborted when the drive wakes up.
0.0
0.0 … 32767.0 Sleep boost step. 1 = 1
40.47 Set 1 wake-up
deviation
When 40.41 Set 1 sleep mode is set to Internal, this
parameter defines the wake-up level as deviation between
process setpoint and feedback. The unit is selected by
parameter 40.12 Set 1 unit selection.
When the deviation exceeds the value of this parameter, and
remains there for the duration of the wake-up delay (40.48
Set 1 wake-up delay), the drive wakes up.
See also parameter 40.31 Set 1 deviation inversion.
0.00 rpm, %
or Hz
-32768.00 …
32767.00 rpm, % or
Hz
Wake-up level (as deviation between process setpoint and
feedback).
1 = 1 unit
40.48 Set 1 wake-up
delay
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter 40.47 Set 1 wake-up
deviation.
The delay timer starts when the deviation exceeds the wake-
up level (40.47 Set 1 wake-up deviation), and resets if the
deviation falls below the wake-up level.
0.50 s
0.00 … 60.00 s Wake-up delay. 1 = 1 s
40.49 Set 1 tracking mode Activates (or selects a source that activates) tracking mode.
In tracking mode, the value selected by parameter 40.50 Set
1 tracking ref selection is substituted for the PID controller
output. See also section Tracking (page 105).
1 = Tracking mode enabled
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
No. Name/Value Description Def/FbEq16