Parameters 417
62.151 INU-LSU data set
11 data 1 sel
(Parameters 62.15162.203 only visible when supply unit
control activated by 95.20)
Parameters 62.15162.153 define a target for the data
received in data set 11 from another converter (typically the
supply unit of the drive).
Parameters 62.20162.203 display the data received from
the other converter in integer format, and can be used as
sources by other parameters.
For example, this parameter selects a target for word 1 of
data set 11. Parameter 62.201 INU-LSU data set 11 data 1
value displays the received data in integer format, and can
also be used as a source by other parameters.
LSU SW
None None. 0
LSU SW Status word of the supply unit. 4
Other Source selection (see Terms and abbreviations on page 148). -
62.152 INU-LSU data set
11 data 2 sel
Defines a target for the data received as word 2 of data set
11.
See also parameter 62.202 INU-LSU data set 11 data 2
value.
For the selections, see parameter 62.151 INU-LSU data set
11 data 1 sel.
None
62.153 INU-LSU data set
11 data 3 sel
Defines a target for the data received as word 3 of data set
11.
See also parameter 62.203 INU-LSU data set 11 data 3
value.
For the selections, see parameter 62.151 INU-LSU data set
11 data 1 sel.
None
62.201 INU-LSU data set
11 data 1 value
Shows (in integer format) the data received from the other
converter as word 1 of data set 11.
A target for this data can be selected by parameter 62.151
INU-LSU data set 11 data 1 sel. The value can also be used
as a source by another parameter.
0
0…65535 Data received as word 1 of data set 11.
62.202 INU-LSU data set
11 data 2 value
Shows (in integer format) the data received from the other
converter as word 2 of data set 11.
A target for this data can be selected by parameter 62.152
INU-LSU data set 11 data 2 sel. The value can also be used
as a source by another parameter.
0
0…65535 Data received as word 2 of data set 11.
62.203 INU-LSU data set
11 data 3 value
Shows (in integer format) the data received from the other
converter as word 3 of data set 11.
A target for this data can be selected by parameter 62.153
INU-LSU data set 11 data 3 sel. The value can also be used
as a source by another parameter.
0
0…65535 Data received as word 3 of data set 11.
No. Name/Value Description Def/FbEq16