Start-up 81
Comm control Commits the changes in the EFB
settings or activates the silent mode.
Enabled Normal operation.
Refresh settings Commits the modified EFB settings.
Reverts automatically to Enabled.
Silent mode Activates the silent mode (no
messages are transmitted).
The silent mode can be canceled
with the Refresh settings item.
Comm diagnostics
Bit positions:
Status of the EFB communication.
Read-only parameter.
0 – Init failed 1 = EFB initialization failed
1 – Addr config err 1 = Node address not allowed by
protocol
2 – Silent mode 1 = Inverter not allowed to transmit
0 = Inverter allowed to transmit
3 – Autobauding 1 = Inverter attempting to determine
transfer rate
4 – Wiring error 1 = Errors detected (Data+/Data-
wires possibly swapped)
5 – Parity error 1 = Error detected: Check the Baud
rate and Parity parameters.
6 – Baud rate error 1 = Error detected: Check the Baud
rate and Parity parameters.
7 – No bus activity 1 = 0 bytes received in last 5
seconds.
8 – No packets 1 = 0 packets (addressed to any
device) detected in last 5 seconds.
9 – Noise or addressing
error
1 = Errors detected: Interference or
another device online with the same
address.
10 – Comm loss 1 = 0 packets addressed to the
inverter received within timeout.
11 – CW/Ref loss 1 = No control word or references
received within timeout.
12 – Not active Reserved.
13 – Protocol 1 1 = Protocol-dependent status
information.
14 – Protocol 2 1 = Protocol-dependent status
information.
15 – Internal error 1 = Problem with the calls to the
inverter control program.
To set up the remote monitoring interface: