82 Start-up
Received packets 0…4294967295 Count of the received valid packets
addressed to the inverter. In normal
operation, the number increases
constantly.
To reset the count, push the Reset
button on the control unit for 3
seconds.
Transmitted packets 0…4294967295 Count of the transmitted valid
packets addressed to the inverter. In
normal operation, the number
increases constantly.
To reset the count, push the Reset
button on the control unit for 3
seconds.
All packets 0…4294967295 Count of the valid packets
addressed to any device on the bus.
In normal operation, the number
increases constantly.
To reset the count, push the Reset
button on the control unit for 3
seconds.
UART errors 0…4294967295 Count of the character errors
received by the inverter. An
increasing count indicates a
configuration problem.
To reset the count, push the Reset
button on the control unit for 3
seconds.
CRC errors 0…4294967295 Count of the packets with a CRC
error received by the inverter. An
increasing count indicates
interference on the bus.
To reset the count, push the Reset
button on the control unit for 3
seconds.