IEC09000722-2-en.vsd
IEC09000722 V2 EN-US
Figure 96: CMT: Container window design when selecting DNP3 protocol
Procedure to move signals:
1. Select one or several signals.
Click in the list of signals to select one signal.
Press Shift or Ctrl and several signals to select a set of signals.
Right-click in the list of signals, select Select All from the context menu
or press Ctrl+A to select all signals.
2. Press the blue arrow button to insert the selected signals into the configuration.
3. Press the green double arrow button to insert all signals into the configuration,
see
Figure 97.
IEC08000361.vsd
IEC08000361 V1 EN-US
Figure 97: CMT: Move buttons
4. Click the drop down list Signal Type: to select the other signal types for this
channel.
5. Repeat to move signals for all signal types and save the selection.
Content changes in the DNP3 container are marked with a star at
the end of the name, see Figure 98. The star indicates that changes
in the container have to be saved before leaving CMT.
IEC08000339-2-en.vsd
IEC08000339 V2 EN-US
Figure 98: CMT: Marker to indicate changes in the container
1MRK 511 398-UEN C Section 10
DNP3 communication engineering
670 series 2.2 IEC 141
Engineering manual