A1-User’s Manual
96
10.35 VFD overload warning level
Range: 10.0 ~ 200.0 % in 0.1 %
Initial value: 100.0 %
Program a level of the VFD motor current
10.36 FA2 reference at acceleration
Range: '10.37 ' ~ 400Hz in 0.01 Hz
Initial value: 0.0 Hz
Program the frequency arrival threshold during acceleration
Related Parameters: '10.26'
10.37 FA2 reference at deceleration
Range: 0.00 ~ '10.36' Hz in 0.01 Hz
Initial value: 0.0 Hz
Program the frequency arrival threshold during deceleration
Related Parameters: '10.26'
10.38 PID Error tolerance
Range: 0.0 ~ 100.0 % in 0.1 %
Initial value: 100.0 %
Program the allowable PID loop error magnitude
Related Parameters: '10.26'