A1-User’s Manual
121
22.25 UP/DOWN function
0: Disable ----- Initial value
1: Enable
Run command
DOWN
UP
F
ON ON
ON
ON
ON
22.26 UP/DOWN initial value
Range: 0.00 ~ 400 Hz in 0.01 Hz - frequency
Range: 0.0 ~ 100 % in 0.1 % - PID
Initial value: 0.00 Hz
Program the UP/DOWN initial value
When run command is input, VFD is running to initial value without up or down source
22.27 UP/DOWN up source
0: Not selected ----- Initial value
1: Selected
2: DI1
3: DI2
4: DI3
5: DI4
6; DI5
7: DI6
8: DI7
9: DI8
Selects the source of the UP/DWON up
Set 0: Not selected
Always off
Set 1: selected
Always on
Set 2~9 : DI1~ DI8
It works by digital input which is selected
22.28 UP/DOWN down source
See the parameter '20.27' (UP/DOWN up source)