23.10 Acceleration time transition frequency
Range: 0.00 ~ 400Hz in 0.01 Hz
Initial value: 0.00 Hz
In addition to acceleration time 1 in
'23.04' (Acceleration time 1),
'23.06' (acceleration
time 2)
can be specified. Its value can also be entered by
'23.03' (Ramp set selection)
Related Parameters:
'23.03', '23.04', '23.06'
23.11 Deceleration time transition frequency
Range: 0.00 ~ 400Hz in 0.01 Hz
Initial value: 0.00 Hz
In addition to deceleration time 1 in
'23.05' (Deceleration time 1),
'23.07' (Deceleration
time 2)
can be specified. Its value can also be entered by
'23.03' (Ramp set selection)
Related Parameters:
'23.03', '23.05, '23.07'
23.12 Jogging acceleration time
Range: 0.0 ~ 3000 Sec in 0.1 Sec
Initial value: 30.0 Sec
It works when the jogging is operated
Related Parameters:
'22.17', '22.18'
23.13 Jogging deceleration time
Range: 0.0 ~ 3000 Sec in 0.1 Sec
Initial value: 30.0 Sec
It works when the jogging is ON
Related Parameters:
'22.17', '22.18'
23.14 Emergency stop time
Range: 0.0 ~ 3000 Sec in 0.1 Sec
Initial value: 3.0 Sec
It works when the emergency source is ON
Related Parameters:
'21.11'