18 ControlLogix Redundancy System Overview
Making Online Edits
Online edits automatically crossload to the secondary controller. They
become inactive if a switchover happens before you assemble them
into the project. This stops a mistake from faulting both the old and
new primary controllers.
Suppose you test an online edit and it causes the controller to fault. In
that case, a switchover happens. The new primary controller
automatically untests the edits and goes back to the original code.
You have the option to keep the edits active after a switchover (at the
risk of faulting both controllers).
Increasing Scan Time
At the end of each program, the primary controller pauses its
execution to crossload the result of any output instruction that
executed in the program. This results in an increased program scan
time for a synchronized redundancy system.
Scan Time
Network Addresses During
a Switchover
Each CNB, ENBT, or EWEB module in a redundant chassis shares a
pair of network addresses with its partner in the other chassis.
Execute Program in
Primary Controller
Start of Program End of Program
Crossload Results to
Secondary Controller
Program Scan Time

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1756-CNB and is the answer not in the manual?

Allen-Bradley 1756-CNB Specifications

General IconGeneral
BrandAllen-Bradley
Model1756-CNB
CategoryControl Systems
LanguageEnglish

Related product manuals