Publication 1756-UM523F-EN-P - December 2006
100 Configure and Program the Controller
Set Task Watchdog Times
To give a redundant controller longer watchdog times than a
nonredundant controller, perform this procedure.
After a switchover, the secondary controller starts the scan at the
beginning of the program that was running in the primary
controller at the time of the switchover.
The watchdog timer for the task that has the program, however,
is not reset.
A major fault happens (type 6, code 1) if the watchdog timer has
too little time to completely rescan the program.
Action Details
1. Set the minimum watchdog time for a
task.
Use this formula to set the minimum watchdog time for a task:
Minimum watchdog time = (2 * maximum_scan_time) + 150 ms
where:
Maximum_scan_time is the maximum scan time for the entire task when the
secondary controller is synchronized.
2. Set the estimated watchdog time for a
task.
C. Type a watchdog time that is
more than the watchdog time
from step 1.
B. Click Configuration.
D. Choose OK.
Controller Primary
Tasks
MainTask
+
+
A. Right-click the task and choose Properties.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1756-CNB and is the answer not in the manual?

Allen-Bradley 1756-CNB Specifications

General IconGeneral
BrandAllen-Bradley
Model1756-CNB
CategoryControl Systems
LanguageEnglish

Related product manuals