EasyManua.ls Logo

Allen-Bradley MicroLogix 1400 - Page 186

Allen-Bradley MicroLogix 1400
694 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1766-RM001A-EN-P - October 2008
184 Timer and Counter Instructions
CTD Instruction Counter Control and Status Bits, Counter Word 0
(Data File 5 is configured as a timer file for this example.)
Bit Is Set When: And Remains Set Until One of the Following
Occurs:
bit 11 - C5:0/UN UN - underflow
indicator
the accumulated value wraps from
-32,768…+32,767 and continues to count
down
a RES instruction with the same address as the
CTD instruction is enabled
bit 13 - C5:0/DN DN - done
indicator
accumulated value
preset value accumulated value < preset value or,
a RES instruction with the same address as the
CTU instruction is enabled
bit 14 - C5:0/CD CD - count down
enable
rung state is true rung state is false
a RES instruction with the same address as the
CTD instruction is enabled
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive