EasyManua.ls Logo

Allen-Bradley MicroLogix 1400 - Possible Error Codes for Socket Services

Allen-Bradley MicroLogix 1400
694 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1766-RM001A-EN-P - October 2008
508 Socket Interface Using CIP Generic Messaging
Configure the MSG with these values:
N file for sending contains : 0 bytes
- NONE
N file for receiving contains : 0 bytes
- NONE
Possible Error Codes for
Socket Services
If the Socket Object encounters an error with a service request, or while
processing the service request:
The Socket Object returns an error code.
The MSG instruction sets the MGx:y/ER bit.
The MSG instruction sets error codes in Word 18(MGx:y.ERR) of MG
file. Low byte is error code 0xDE (Object Specific General Error) and
high byte is 0.
The MSG instruction sets internal fail code in Word 22(MGx:y.22) of
MG file. Low byte is error code 0xDE (Object Specific General Error)
and high byte of this sub-element contains detailed extended error
code.
CIP Generic Msg Parameter Description
Channel 1 (Integral)
Communication Command CIP Generic
Service Custom
Service Code 51 (hexadecimal)
Class 342 (hexadecimal)
Instance 0
Attribute 0
Data Table Address (Send) Not used.
Size in Bytes (Send) 0 bytes
Data Table Address (Receive) Not used.
Size in Bytes (Receive) 0 bytes
Extended Routing Info File(RIX) Specify RIX file
To Address in MultiHop tab 127.0.0.1
Considerations :
Call the DeleteAllSockets service with instance 0.
A typical use of DeleteAllSockets is when application development and debugging is complete.