Publication 1766-RM001A-EN-P - October 2008
Communications Instructions 411
When the Communications Servicing Selection bit is unchecked, at the
next execution of a Service Communications (SVC) instruction, I/O
Refresh (REF) instruction, or when it performs Communications Servicing,
whichever occurs first, commands/replies are processed as follows:
• One incoming channel 0 or channel 1 command;
• (conditional) If the Message Servicing Selection is clear (not
checked) first, all incoming channel 0 or channel 1 message replies;
then all outgoing channel 0 or channel 1 messages on the overflow
queue. If the Message Servicing Selection is set (checked), First the
incoming channel 0 or channel 1 message reply; then one outgoing
channel 0 or channel 1 message on the overflow queue.
• All remaining incoming channel 0 or channel 1 commands.
Message Servicing Selection
Use this check box to enhance communication capability. If this is
checked and the Communication Servicing Selection check box is not
checked the MSG functionality throughput (and scan time) will increase.
• When this check box is checked, the controller services one
outgoing channel 0 or channel 1 MSG instruction at the next Service
Communications (SVC) instruction, I/O Refresh (REF) instruction, or
when it performs Communications Servicing. When this check box
is clear (unchecked), the controller services all outgoing channel 0
or channel 1 MSG instructions at the next Service Communications
(SVC) instruction, I/O Refresh (REF) instruction, or when it performs
Communications Servicing.
• The Message Servicing Selection (Channel 0 or channel 1) bit is
applied by the controller when the Communications Servicing
Selection (Channel 0 or channel 1) bit is clear (unchecked).
MSG Instruction Ladder
Logic
Enabling the MSG Instruction for Continuous Operation
The message instruction is enabled during the initial processor program
scan and each time the message completes. For example, when the DN or
ER bit is set.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1400 and is the answer not in the manual?

Allen-Bradley MicroLogix 1400 Specifications

General IconGeneral
Processor32-bit
Expansion ModulesUp to 7 expansion I/O modules
Power Supply24V DC or 120/240V AC
Programming SoftwareRSLogix 500
Communication PortsEthernet, RS-232/RS-485 combo port
Controller TypeProgrammable Logic Controller (PLC)
SeriesMicroLogix
Digital Outputs12
Analog Inputs6 (embedded)
Analog Outputs2 (embedded)
High-Speed Counter6 high-speed counters
Pulse Output2 (embedded)
Ethernet PortYes

Related product manuals