Publication 1766-RM001A-EN-P - October 2008
ASCII Instructions 391
7 0x07 The instruction cannot be executed because the
communications channel has been shut down via the
channel configuration menu.
Reconfigure the channel and retry operation.
8 0x08 The instruction cannot be executed because another
ASCII transmission is already in progress.
Resend the transmission.
9 0x09 Type of ASCII communications operation requested
is not supported by the current channel
configuration.
Reconfigure the channel and retry operation.
10 0x0A The unload bit (UL) is set, stopping instruction
execution.
None required.
11 0x0B The requested number of characters for the ASCII
read was too large or negative.
Enter a valid string length and retry operation.
12 0x0C The length of the Source string is invalid (either a
negative number or a number greater than 82).
Enter a valid string length and retry operation.
13 0x0D The requested length in the Control field is invalid
(either a negative number or a number greater than
82).
Enter a valid length and retry operation.
14 0x0E Execution of an ACL instruction caused this
instruction to abort.
None required.
15 0x0F Communications channel configuration was changed
while instruction was in progress.
None required.
Table 21.4
Error Code Description Recommended Action
decimal hexadecimal
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1400 and is the answer not in the manual?

Allen-Bradley MicroLogix 1400 Specifications

General IconGeneral
Processor32-bit
Expansion ModulesUp to 7 expansion I/O modules
Power Supply24V DC or 120/240V AC
Programming SoftwareRSLogix 500
Communication PortsEthernet, RS-232/RS-485 combo port
Controller TypeProgrammable Logic Controller (PLC)
SeriesMicroLogix
Digital Outputs12
Analog Inputs6 (embedded)
Analog Outputs2 (embedded)
High-Speed Counter6 high-speed counters
Pulse Output2 (embedded)
Ethernet PortYes

Related product manuals