Publication 1766-RM001A-EN-P - October 2008
516 Recipe and Data Logging
Application Explanation of Operation
When B3:0/0 is energized and B3:0/1 and B3:0/2 are de-energized, Recipe
File 0:Recipe number 0 is executed loading the following values to create
Yellow paint.
• N7:0 = 500
• N7:1 = 500
• N7:2 = 0
• T4:0.PRE = 500
When B3:0/1 is energized and B3:0/0 and B3:0/2 are de-energized, Recipe
File 0:Recipe number 1 is executed loading the following values to create
Purple paint.
• N7:0 = 500
• N7:1 = 0
• N7:2 = 500
• T4:0.PRE = 500
When B3:0/2 is energized and B3:0/0 and B3:0/1 are de-energized, Recipe
File 0:Recipe number 2 is executed loading the following values to create
White paint.
• N7:0 = 333
• N7:1 = 333
• N7:2 = 333
• T4:0.PRE = 1000
Monitor the N7 data file. Notice the values change after each bit is
toggled.
This example describes loading values from a RCP file to data table
addresses. However, note that by changing the RCP file operation from
Load to Store, values can be loaded by ladder logic into the recipe
database for each Recipe number.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive