EasyManua.ls Logo

Allen-Bradley MicroLogix 1400 - Page 557

Allen-Bradley MicroLogix 1400
694 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1766-RM001A-EN-P - October 2008
System Status File 555
Forces Enabled
This bit is always set (1) by the controller to indicate that forces are
enabled.
Forces Installed
This bit is set (1) by the controller to indicate that 1 or more inputs or
outputs are forced. When this bit is clear, a force condition is not present
within the controller.
Address Data Format Range Type User Program Access
S:1/5 binary 1 status read only
Address Data Format Range Type User Program Access
S:1/6 binary 0 or 1 status read only