Publication 1766-RM001A-EN-P - October 2008
Knowledgebase Quick Starts 657
The following outlines the configuration and steps that can be used to
read data log records from an MicroLogix 1400 controller remotely via a
1747CH0RAD (Remote Access Modem Kit)
This example assumes that the programmer has configured the DLG
instruction in the ML1400 to log data and that HyperTerminal is installed,
configured and the user is familiar with its use.
ESTABLISHING CONNECTIONS
1. Connect the modem to Channel 0 of the ML1400
2. Configure Channel 1 (9-Pin) for DF1 Full Duplex, 9600 baud, no
parity, and full duplex modem handshaking. This setting is critical,
as the system will not communicate if full duplex modem
handshaking isn't applied to the comms channel connected to the
modem.
3. Configure HyperTerminal for direct connection to the PC COMM
port the modem is connected to. Make sure the HyperTerminal
connection is configured for 9600 baud.
4. Save configuration as “DataLog “.
5. Send the following dial-out string using HyperTerminal to dial the
modem and establish the connection:
AT&C1DT(Phone number of destination Modem) then press
enter
your modem will respond: CONNECT 9600
Once the connection is established, exit HyperTerminal by selecting File/
Exit from the pull-down menu. When asked “Do you want to close
connection” select Yes. This will only close the connection from
HyperTerminal to the RS-232 port. The connection will remain active.
FYI - It will appear as though HyperTerminal has disconnected. It
has not; the connection is still established only HyperTerminal is no
longer running.
6. Open the Data Logging Utility.
7. Select in the DLG Utility the COMM port that the PC modem is
configured for.
8. Click Connect.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1400 and is the answer not in the manual?

Allen-Bradley MicroLogix 1400 Specifications

General IconGeneral
Processor32-bit
Expansion ModulesUp to 7 expansion I/O modules
Power Supply24V DC or 120/240V AC
Programming SoftwareRSLogix 500
Communication PortsEthernet, RS-232/RS-485 combo port
Controller TypeProgrammable Logic Controller (PLC)
SeriesMicroLogix
Digital Outputs12
Analog Inputs6 (embedded)
Analog Outputs2 (embedded)
High-Speed Counter6 high-speed counters
Pulse Output2 (embedded)
Ethernet PortYes

Related product manuals