Basic Operation 12 (258)
3.2 Network Identity
By default, the module identifies itself as a generic Anybus implementation as follows:
Device ID 0010h (Anybus CompactCom 40 PROFINET)
Vendor ID 010Ch (HMS Industrial Networks)
Station Type The Station Type will be assigned a value according to this priority:
If the PROFINET IO Object (F6h) is implemented, the value equals that of
attribute #3 in instance #1.
If the PROFINET IO Object is not implemented, the value of attribute #9 (Product
name) in the Application Object (FFh), instance #1, will be used (if implemented).
If none of these attributes are implemented, the value equals Anybus
CompactCom default value (“ABCC-PIR”).
It is recommended to customize the identity information so that the Anybus module appears as
a vendor specific implementation rather than a generic Anybus product.
See also...
• Identification & Maintenance (I&M), p. 24
• PROFINET IO Object (F6h), p. 184
• Application Object (FFh) in Anybus CompactCom Software Design Guide
3.3 Communication Settings
Network related communication settings are grouped in the Network Configuration Object
(04h), and includes:
Ethernet Interface
Settings
The module is locked to 100 Mbit full duplex operation as required by PROFINET.
IP Settings These settings must be set in order for the module to be able to participate on the
network.
Normally set by the IO Controller.
SMTP Account
Settings
These settings must be set in order for the module to be able to send e-mail
messages.
PROFINET Station
Name
The module needs to be assigned a Station Name in order to participate on
PROFINET.
Normally set from the network.
See also...
• Identification & Maintenance (I&M), p. 24
• Web Server, p. 38
• Network Configuration Object (04h), p. 99
• Secure HICP (Secure Host IP Configuration Protocol), p. 215