Appendix G: Conformance Test Guide 228 (258)
G.9 Changes in GSD File for Conformance Class B
The example GSD file, supplied by HMS Industrial Networks AB, is adapted for testing a Any-
bus CompactCom 40 PROFINET IRT for conformance class C. If the implementation does not
need the isochronous features of the device, the GSD file can be modified to mirror this. The im-
plementation can then be conformance tested for conformance class B instead. The list below
describe the changes needed in the example GSD file to accomplish this.
1. The value of the ConformanceClass attribute in the <CertificationInfo...> ele-
ment in each DAP must be changed from “C” to “B”.:
<CertificationInfo ConformanceClass="B" ApplicationClass=""
NetloadClass="III"/>
2. The value of the SupportedRT_Classes attribute in the <InterfaceSubmoduleItem
...> element in each DAP must be “RT_CLASS_1”. I.e. “RT_CLASS_3” must be
removed:
<InterfaceSubmoduleItem ID="Interface" SubslotNumber="32768"
SubmoduleIdentNumber="0x00000002"
SupportedRT_Classes="RT_CLASS_1" TextId="T_ID_INTERFACE"
SupportedProtocols="SNMP;LLDP" SupportedMibs="MIB2" DCP_
HelloSupported="true"
PTP_BoundarySupported="true" DCP_BoundarySupported="true"
DelayMeasurementSupported="true">
3. The elements <RT_Class3Properties ...>, <SynchronisationMode ...>, and
<RT_Class3TimingProperties ...> must be removed from each DAP
G.10 SYNC Pin Measurements for Conformance Class C Test
For a conformance class C (IRT) test, access to the SYNC pin must be provided to the test lab.