Anybus Module Objects 144 (258)
Command Details: Appl_State_Ready
Category
Extended
Details
Command Code: 15h
Valid for: Object Instance
Description
This command is only applicable if the host application implements support for End_Of_Prm_Ind, and sig-
nals to the module (and in turn the I/O Controller) that the host application is ready for data exchange.
• Command Details
Field Contents Comments
CmdExt[0] AR handle (low byte) Handle for the Application Relationship (AR)
CmdExt[1] AR handle (high byte)
See also...
Application Process Instances (API), p. 18
• End_Of_Prm_Ind, command details in PROFINET IO Object (F6h), p. 184
Command Details: AR_Abort
Category
Extended
Details
Command Code: 16h
Valid for: Object Instance
Description
This command indicates to the module that the current application relationship shall be aborted.
• Command Details
Field Contents Comments
CmdExt[0] AR handle (low byte) Handle for the Application Relationship (AR)
CmdExt[1] AR handle (high byte)
See also...
– Application Process Instances (API), p. 18
– AR_Check_Ind, command details in PROFINET IO Object (F6h), p. 184
– Expected_Ident_Ind, command details in PROFINET IO Object (F6h), p. 184
– Appl_State_Ready, command details in PROFINET IO Object (F6h), p. 184
Anybus
®
CompactCom
™
40 PROFINET IRT Network Guide SCM-1202-023 EN 1.8