SH-300
User’s Manual Connection with PLC
Page 101 of 103
4.20 Array TC-Pro Series Digital Timer/Counter/Tachometer
SH-300 can communicate with Array TC-Pro Series digital timer/counter/tachometer through
communication port.
SH-300 software configuration:
Item
Content
SH-300 COM port
9 pin COM port
PLC COM port
Programming port
Default parameter
9600bps7bits1stopEven
Station No.
0-254, default value: 0
Distance (Max.)
15m
Communication type
RS232
Cable type
CAB-090A232
The description of address types used in SH300 software:
Note: TC-Pro Series digital timer/counter/tachometer use Hex addresses. the register value is
displayed in BCD.
Object
type
Address
type
Address range
Read/
Write
Description
Indicator
M
Refer to address list
for details
Read
Read reset signal and output status of
timer/counter/tachometer
Register
D
Refer to address list
for details
Read/
Write
Read and write the register value of
timer/counter/tachometer
Dynamic
text
D
Refer to address list
for details
Read
Read the register value of
timer/counter/tachometer
Bar
graph/
Trend
graph
D
Refer to address list
for details
Read
Read the register value of
timer/counter/tachometer