155
Installing the S8700 IP Connect
May 2002
Reset LEDs on Power Distribution Unit
A red LED next to any of the 32 power output connectors indicates a short circuit in the
building wiring or the terminal equipment. To reset the LED:
1 Disconnect the terminal equipment from the wall jack.
2 If the LED goes off, the terminal equipment is faulty and must be replaced. If the LED is
still lit, find and repair the short circuit in the building wiring.
3 Reconnect the terminal equipment to the wall jack and re-test terminal equipment
operation.