56
Installing the S8700 IP Connect
May 2002
Connect Media Gateway Grounds and Other
Grounds
Follow these additional grounding requirements:
• The approved ground wire must be green, 6 AWG (#40) (16 mm
2
), copper, stranded
wire. This is in addition to the ground wire in the AC power cord.
• Bond allapproved grounds at the single-point ground to form a single grounding
electrode system.
Connect the cable as shown in ‘‘Single-media gateway RMC grounding’’ on page 56
for an
Avaya G600 single Media Gateway, or ‘‘Multi-media gateway RMC grounding’’ on page 57
for
two or more Avaya G600 Media Gateway.
Single-media gateway RMC grounding
Figure notes
1 10 AWG (#25) (6 mm
2
) wire
to coupled bonding
conductor (CBC).
2 6 AWG (#40) (16 mm
2
) ground
wire from single-point ground
block to the approved building
ground.
1
2
cadpgnd1 LJK 102500