Installing the S8700 IP Connect
May 2002
3 Administer the emulation program port settings:
9600 baud rate
No parity
8 bits
1 stop bit
4 Press Enter. The Main Configuration screen appears. If the Main Configuration screen
does not appear, press
Enter again.
5 Type BR 0 and press Enter. (Sets the BOOTP retry counter to zero.)
6 Type IP 198.152.254.239 and press Enter. (Default IP Address for this UPS)
7 Type NM 255.255.255.0 and press Enter. (Default subnet mask for this UPS)
8 Type GW 198.152.254.201 and press Enter. (Default gateway for this UPS)
NOTE:
If a Network Management System (NMS) is going to monitor the UPS units, coordinate
the assignment of community names with the LAN administrator (refer to the Job Aid
entitled Pre-Installation Network WorksheetS8700 IP Connect
). If an NMS is not
going to monitor the UPSs, set the community names to unique string values.
9 If supplied, enter the Get and Set community names with the following commands:
Type CG name and press Enter. (Enters the Get community name. Type up to 16
alphanumeric characters fo the name. The name field is case sensitive and cannot
contain blanks.)
Type CS name and press Enter. (Enters the Set community name. Type up to 16
alphanumeric characters for the name. The name field is case sensitive and cannot
contain blanks.)
10 Type HS and press Enter. (Displays the Host Table)
NOTE:
The Host Table should be empty. If not, in the following commands use a host table entry
that is currently unassigned.
11 Type HI1 198.152.254.201 and press Enter. (Sets the trap destination for this UPS)
12 Type TL1 3 and press Enter. (Sets the trap level for the host, All traps)
13 Type TT1 1and press Enter. (Sets the trap type, Standard UPS MIB-defined)
14 Type HS and press Enter. Verify the table entries. (Redisplays the host table)
15 Type CF and press Enter. (Redisplays the basic administration screen)
16 Type SA and press Enter. (Saves configuration and restarts module)
17 When completed, disconnect the services laptop computer from the UPS.
18 Connect one end of a CAT5 cable to the RJ45 connector on the UPS 1 SNMP module
and the other end to the next available port on an Ethernet switch.