• When parameters are set the value is automatically stored
in the internal memory.
• When r000 is selected (and P005=21), the display shows the
the actual frequency or when the drive is stopped, the
display flashes every 1.5 seconds the frequency setpoint..
• The speed of the drum can be changed on the fly when you
use the UP or DOWN buttons to change the output frequency
in r000.
• If the acceleration or deceleration of the frequency is too
fast the MicroMaster goes into a protective mode for a
while and then continues. The output frequency is reduced
until the current falls below its limit.
During this process the display flashes as warning.
Increase the time for acceleration or deceleration to avoid
this phenomenon.
• Parameter 964 shows the software version
• In the event of a failure the converter switches off and an
error code appears in the display. The last recorded error
is stored in parameter number 947[8].
Short Error list:
ERROR description
F001
overcurrent
F002
overvoltage
F003
under voltage
F004
inverter over temperature
F005
inverter I2T
F010
motor over temperature
F015
PTC not present
F008
USS protocol timeout
F501
current limit
F502
over voltage limit
When the fault has been corrected the converter can be reset
by pressing the button “Fn:
Remark :
complete list of errors can be found in the Siemens manual
This is a list of all parameters, which are different from the default values.
Parameters