Field Service Manual December 2003
Page 104 of 276
When for the first time parameters are put inside the micromaster start with setting p010 to
1(quick commissioning).
And fill in the following parameters.
At the end don’t forget to put parameter 3900 to 3. At that moment all motorparameters are
calculated.
P3900(=3) calculates some parameters depending on motordata, voltage, curent, speed…
Drum Speed Stability :
Drum speed stability seems to be a issue when umaster is cold
Solution:
Par 1910 should be put on 1 and then the motor should be started with belt
disconnected ! !
A message appears A…
The busy sign will shown on the umaster.
After some time the normal display reappears and you can start using the umaster.
P1910 is for measuring different motor parameters.
Parameters Value Comments
R001 read only
P003 3 3 = expert( See all
params)
P005 21 21= freq / 27=current
P010 0 1=quick commissioning
P100 0 0 50 Hz operation
2 60 Hz operation USA !!
Rpm
P320 0 Motor magnetizing
current
P335 0 Motor cooling
P340 0 1= calculation (once)
P341 0.676
P342 375
P601 0 0 = no sensor ptc
P640 180 Motor overload factor
P700 2 1=BOP / 2 = digital input