Zone Term. 008
DDDDrrrr Board
The line at the top shows the zones available (8 in the
example).
The bottom line shows the standby status and the su
-
pervision relevant to the zones on the device indicated
on the right side, as follow:
Ø
–, the zone is not used;
Ø
O, the zone is Normally Open, Not Supervised;
Ø
C, the zone is Normally Closed, Not Supervised;
Ø
S, the zone is Normally Closed and Supervised with
a Single End of Line Resistance;
Ø
D, the zone is Normally Closed and Supervised with
a Double End of Line Resistance;
Ø
T, the zone is Normally Closed and Supervised with
a Triple End of Line Resistance (Grade 3 Control
Panels ONLY);
Ø
r, the zone is Reserved;
Ø
X, the relative terminal is an output;
Ø
Board are the zones on the Main Board;
Ø
Ein01 are the zones on the Input Expander 01.
5. Press the number relative to a Zone to change its
standby status and supervision option: press 1 for
zone terminal T1, 2 for zone terminal T2 e so on;
press the number until the display shows the re
-
quired option.
Press the key A or B to change the options for all
terminals.
Press the key C or D to select the device.
Press ENTER when the display shows the required
standby status for each zone:
Delayed Zone 000
iiiiiiii Board
The top line shows the number of Delayed Zones.
The bottom line shows the status of the Delayed Option
for each zone on the device indicated on the right side,
as follow:
Ø
–, the zone is not used;
Ø
i, the zone is Instant;
Ø
r, the zone is Reserved;
Ø
D, the zone is Delayed;
Ø
M, the zone has been Modified by BOSS;
Ø
Board are the zones on the Main Board;
Ø
Ein01 are the zones on the Input Expander 01.
+
The r letter next a zone indicates that it is reserved.
These reserved zones are set as Hold-up, Zone
Fault, Internal Siren Fault and External Siren Fault.
+
The M letter next to a zone indicates that the zone’s
delay options (Entry Delay and Exit Delay) were
changed by BOSS, in a configuration DOES NOT
supported by the Wizard Setup then NOT modifi
-
able by the Wizard Setup.
6. Press the number relative to a Zone to change its
Delayed option: press 1 for zone terminal T1, 2 for
zone terminal T2 so on; press the number until the
display shows the required option.
Press the key C or D to select the device.
Press ENTER when the display shows the required
Delayed option for each zone:
Int. Zone 008
IIIIIIII Board
The top line shows the number of Internal Zones.
The bottom line shows the status of the Internal Option
for each zone on the device indicated on the right side,
as follow:
Ø
–, the zone is not used;
Ø
I, the zone is Internal;
Ø
r, the zone is Reserved;
Ø
E, the zone is NOT Internal (Normal);
Ø
Board are the zones on the Main Board;
Ø Ein01 are the zones on the Input Expander 01.
7. Press the number relative to a Zone to change its
Internal option: press 1 for zone terminal T1, 2 for
zone terminal T2 e so on; press the number until the
display shows the required option.
Press the key C or D to select the device.
Press ENTER when the display shows the required
Internal option for each zone:
Sep/09/09 09:14
Bentel Absoluta
The top line shows date and time and the bottom line
shows Bentel Absoluta, indicating the end of the
wizard setup.
+
The configuration can be changed during the pro
-
gramming session.
ABSOLUTA INSTALLING 37
TEMPERATURE (°C) -10 -5 0 5 10 15 20 25 30 35 40 45 50
VOLTAGE (V) 14.5 14.4 14.3 14.1 14.0 13.9 13.7 13.6 13.5 13.4 13.3 13.2 13.1
Table 7 Switching Power Supply Output Voltage chart. To find the Output Voltage using the chart: — select the near
-
est value to the Probe temperature on the TEMPERATURE (°C) row; read the corresponding value on the VOLTAGE
(V) row; adjust the Output Voltage of the Switching Power Supply to the indicated value. For example, if the Probe tem
-
perature is 22 °C, the Output Voltage of the Switching Power Supply must be set at 13.7 V.