9.1.3 Function code 16, write 16-bit parameter
Example 1:
Writing of parameter
Rated Mech. Power 376 (0x0178) in dataset 4 of frequency inverter with ad-
dress 1.
The rated mechanical power is to be set to 1.5 kW. Parameter
Rated Mech. Power 376 has one dec-
imal place. Thus the value to be sent is 15 = 0x000F.
Request: Master frequency inverter
Response: Frequency inverter Master
ID
Par.No.
isters
The response contains the number of written registers
Example 2:
Writing of non-permissible value 0 in parameter
Rated Mech. Power 376 0x0178) in dataset 2 of fre-
quency inverter with address 3.
Request: Master frequency inverter
Error response: Frequency inverter Master
Field:
ID
The sent exception condition code is the hexadecimal value 0x04 = ERROR SLAVE DEVICE.