9.1.3 Function code 16, write 16-bit parameter
Example 1:
Writing of parameter
Rated Mech. Power 376 (0x0178) in dataset 4 of frequency inverter with ad-
dress 1.
The rated mechanical power is to be set to 1.5 kW. Parameter
Rated Mech. Power 376 has one dec-
imal place. Thus the value to be sent is 15 = 0x000F.
Request: Master frequency inverter
Field
:
MBAP
Unit
ID
Func.
DSet/
ParNo.
No. reg-
isters
No.
Byte
Par.
value
Transaction ID
Protocol ID
Length
nn
nn
nn
nn
00
09
01
10
41
78
00
01
02
00
0F
Response: Frequency inverter Master
Field
:
MBAP
Unit
ID
Func.
DSet/
Par.No.
No. reg-
isters
Transaction ID
Protocol ID
Length
nn
nn
nn
nn
00
09
01
10
41
78
00
01
The response contains the number of written registers
Example 2:
Writing of non-permissible value 0 in parameter
Rated Mech. Power 376 0x0178) in dataset 2 of fre-
quency inverter with address 3.
Request: Master frequency inverter
Field
:
MBAP
Unit
ID
Func.
DSet/
ParNo.
No. reg-
isters
No.
Byte
Par.
value
Transaction ID
Protocol ID
Length
nn
nn
nn
nn
00
09
03
10
41
78
00
01
02
00
00
Error response: Frequency inverter Master
Field:
MBAP
Unit
ID
Func.
Excep.
Transaction ID
Protocol ID
Length
Hex
nn
nn
nn
nn
00
03
03
90
04
The sent exception condition code is the hexadecimal value 0x04 = ERROR SLAVE DEVICE.
46
ACU
Modbus/TCP 10/13

Table of Contents

Other manuals for BONFIGLIOLI Active Cube

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI Active Cube and is the answer not in the manual?

BONFIGLIOLI Active Cube Specifications

General IconGeneral
BrandBONFIGLIOLI
ModelActive Cube
CategoryInverter
LanguageEnglish

Related product manuals