EasyManuals Logo

BONFIGLIOLI Active Cube User Manual

BONFIGLIOLI Active Cube
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
9.2.3 Function code 100 (=0x64), read 32-bit parameter
Example 1:
Reading of parameter
Fixed Frequency 2 481 in dataset 0 of frequency inverter with address 1.
Request: Master frequency inverter
Field
:
MBAP
Unit ID
Func.
DSet/
Par.No.
Transaction ID
Protocol ID
Length
Hex
nn
nn
nn
nn
00
04
01
64
01
E1
Response: Frequency inverter Master
Field:
MBAP
Unit ID
Func.
Par. value
Transaction ID
Protocol ID
Length
Hex
nn
nn
nn
nn
00
06
01
64
00
00
03
E8
The sent hexadecimal value is 0x000003E8 = 1000. Parameter
Fixed Frequency 2 481 has two deci-
mal places. Thus, Fixed Frequency 2 = 10.00 Hz.
Example 2:
Reading of unknown parameter 1600 (0x0640) in dataset 2 of frequency inverter with address 1.
Request: Master frequency inverter
Field:
MBAP
Unit ID
Func.
DSet/
Par.No.
Transaction ID
Protocol ID
Length
Hex
nn
nn
nn
nn
00
04
01
64
26
40
Error response: Frequency inverter Master
Field:
MBAP
Unit ID
Func.
Excep.
Transaction ID
Protocol ID
Length
Hex
nn
nn
nn
nn
00
03
01
E4
04
The exception condition code is the hexadecimal value 0x04 = ERROR SLAVE DEVICE.
10/13
ACU
Modbus/TCP 49

Table of Contents

Other manuals for BONFIGLIOLI Active Cube

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI Active Cube and is the answer not in the manual?

BONFIGLIOLI Active Cube Specifications

General IconGeneral
BrandBONFIGLIOLI
ModelActive Cube
CategoryInverter
LanguageEnglish

Related product manuals