11.4.1.1 Example sequence
In order to start “velocity mode”, the correct sequence must be sent by the PLC.
1
Control word =
0x0000
Disable voltage
1
Status word =
0x0050
Switch On Disabled
2
Modes of operation =
2
(Velocity mode)
3
Control word =
0x0006
Shutdown
Status word =
0x0031
Ready to switch on
4
Control word =
0x0007
Switch On
Status word =
0x0033
Switched On
5
Control word =
0x000F
Enable operation, no change of previous status
if already enabled.
Status word =
0xnn37
Operation enabled
6a
Control word =
0x007F
Starts “Velocity mode” with reference value
from parameter
Override Target Velocity vl
[rpm] 1459.
Status word =
0xnn37
Operation enabled
6b
Control word =
0x006F
1299 S. Special Function Generator:
= “9
-Zero”
Starts “Velocity mode” with reference val-
ue from parameter
Override Target Veloc-
ity vl [rpm]
1459.
1299
S. Special Function Generator:
≠ “9
-Zero”
Starts with reference value with source
from 1299
S. Special Function Generator
Status word =
0xnn37
Operation enabled
6c
Control word =
0x003F
Starts “Velocity mode” with reference value “0”
Status word =
0xnn37
Operation enabled
6d
Control word =
0x002F
1299 S. Special Function Generator:
= “9
-Zero”
Starts “Velocity mode” with reference val-
ue “0”
1299
S. Special Function Generator:
≠ “9
-Zero”
Starts with reference value with source
from 1299 S. Special Function Generator
Status word =
0xnn37
Operation enabled
6e
Control word =
0x005F
Starts “Velocity mode” at current speed cur-
rent ramps will be canceled.
Status word =
0xnn37
Disable voltage
6f
Control word =
0x004F
1299 S. Special Function Generator:
= “9
-Zero”
Starts “Velocity mode” at current speed
current ramps will be canceled.
1299
S. Special Function Generator:
≠ “9
-Zero”
Starts with reference value from source
from 1299 S. Special Function Generator
Status word =
0xnn37
Disable voltage
7
Control word =
0x01xx
HALT: The drive is decelerated at the ramp
Deceleration (Clockwise)
421 or Deceleration
Anticlockwise
423.
Status word =
0xnn37
Operation enabled
80
ACU
Modbus/TCP 10/13

Table of Contents

Other manuals for BONFIGLIOLI Active Cube

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI Active Cube and is the answer not in the manual?

BONFIGLIOLI Active Cube Specifications

General IconGeneral
BrandBONFIGLIOLI
ModelActive Cube
CategoryInverter
LanguageEnglish

Related product manuals