DEACTIVATION
Follow the same activation steps and set “OFF”.
Note: the activation of the continuous cycle function does not
appear on display in standard mode.
3.5.3 Maximum and minimum temperature
monitoring
The control allows you to continuously record the minimum and
maximum temperature measured by the control probe. The monitoring
is always active. The values can be reset, as described below.
After entering the multifunction menu (see previous par.), select with UP
/ DOWN the message “rEc”.
Procedure:
1. press Set; the message “MAX” will appear (maximum registered
temperature); in order to see the maximum temperature, registration
date and time pass to point 3 or:
2. press UP/DOWN: the message “MIn” appears (minimum temperature
registered);
3. press Set: the maximum/minimum recorded temperature will appear
along with the date/time of record (y=year, m = month, d = day, h =
hour, m = minutes. Press UP to cancel (both temperatures), appears
RES and the control exits the menu, or press Prg for more than once
and exit the display.
Example: maximum registered temperature 36.9°C on 22/11/2013 at 9.34.
1 21 2
1 21 2
1 21 2
1 21 2
1 21 2
1 21 2
1 21 2
1 21 2
Note: by pressing UP you will cancel both the maximum and the
minimum recorded temperature.
Note: the Figures refer to the screens on models with single row
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*:
• MAX --> Max temp recorder (scrolling)
• 36,9 --> Max
• 13.Y --> year
• 11.M --> month
• 22.d --> day
• 9.H --> hour
• 34.m --> minute
3.5.4 Input/output status display
After entering the multifunction menu (see previous par.), select with UP
/ DOWN the message “I/O”.
Procedure:
1. Press Set: the message “b1” appears regarding the probe B1;
2. Press Set once again: the value read on probe B1 will appear alternating
with the message b1;
3. Press Prg to return to upper level;
4. Press UP/DOWN and repeat steps 1)…3) to display the inputs/outputs
indicated in table;
5. Press one or more times Prg to return to standard display
Text Description Text Description
b1 Analogue input 1 do2 Digital output 2
b2 Analogue input 2 do3 Digital output 3
b3 Analogue input 3 do4 Digital output 4
b4 Analogue input 4 do5 Digital output 5
b5 Analogue input 5 do6 Digital output 6
di1 Digital input 1 Y1 Analog output 1
di2 Digital input 2 ESu EVD suction temp.
di3 Digital input 3 ESA EVD evaporation temp.
do1 Digital output 1
Tab. 3.f
Note: the opened digital inputs/outputs are displayed along with
the message “oP” (=open), those closed with “cLo” (=closed).
Example 1: probe B1 measures the temperature of -1.0 °C..
1 21 2
1 21 2
1 21 2
1 21 2
Note: the fi gure refers to the screens on models with single row
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*,
as well as the message indicated, during navigation the display shows the
scrolling message “Probe1 status” on the second row “.