6-14
Cisco 1240 Connected Grid Router Hardware Installation Guide
OL-26223-04
Chapter 6 Installing the Router
Additional Router Connections
Cable Glands Description
Figure 6-8 Cable Glands, Assembled
Figure 6-9 Cable Gland Components
Cable Requirements
Cables used with the cable glands should meet the following criteria:
• Outdoor-rated
• UV-stabilized
• Diameter of 0.20-0.35 inches (5.08-8.89 mm)
Caution Cables must be a minimum of 0.20 in. in diameter to create an adequate seal within the cable glands.
Using smaller cables could result in an inadequate seal and therefore expose the router interior to
environmental elements.
300596
Item Name Description
1 Adapter Connects directly to the chassis cable port on the router.
2 Grommet Secures the split gasket over the cable.
3 Split gasket Fits over the cable and creates an liquid-tight seal inside the glands.
4 Cap Fits over gasket-and-cable assembly and connects it to the chassis cable port.
300591
1
2
3
4