833-3577 CB-FALCON SYSTEM OPERATOR INTERFACE
65-0296—01 46 750-241
Auxiliary
pump control
Auto
On
10 19
Auxiliary
pump is on
when
CH pump is ON
DHW pump is ON
CH or DHW pump is ON
Slave command
Auxiliary
pump output
Pump A
Pump B
Pump C
None
Boiler pump
control
Auto
On
Boiler pump
output
Pump A
Pump B
Pump C
None
Boiler pump
overrun time
0-600 seconds
0 = Not configured
CH pump
control
Auto
On
CH pump
output
Pump A
Pump B
Pump C
None
CH pump
overrun time
0-600 seconds
0 = Not configured
CH pump
frost overrun
time
0-600 seconds
0 = Not configured
DHW pump
control
Auto
On
DHW pump
output
Pump A
Pump B
Pump C
None
DHW pump
overrun time
0-600 seconds
0 = Not configured
DHW pump
frost overrun
time
0-600 seconds
0 = Not configured
DHW pump
start delay
0-600 seconds
0 = Not configured
System
pump control
Auto
On
System
pump output
Pump A
Pump B
Pump C
None
System
pump
overrun time
0-600 seconds
0 = Not configured
System
exercise
interval
Days
Pump
exercise time
0-600 seconds
0 = Not configured
Table 42. Configurable Parameters. (Continued)
Parameter Comment
Table
#
Page
#
Auxiliary
pump cycles
0-999,999 11 20
Boiler pump
cycles
0-999,999
Burner cycles 0-999,999
Burner run
time
Hours
CH pump
cycles
0-999,999
DHW pump
cycles
0-999,999
System
pump cycles
0-999,999
DHW high
limit
Enabled
Disabled
12 20
DHW high
limit
response
Suspend DHW
Recycle & hold
Lockout
DHW high
limit setpoint
-40 °C - 130 °C (-40 °F - 266
°F)
Outlet high
limit
response
Recycle & hold
Lockout
Stack limit Enabled
Disabled
13 21
Stack limit
delay
0-600 seconds
Stack limit
response
Lockout
Recycle & delay
Stack limit
setpoint
-40 °C - 130 °C (-40 °F - 266
°F)
Delta-T limit
enable
Enabled
Disabled
14 21
Delta-T limit
delay
0-600 seconds
Delta-T limit
response
Recycle & delay
Lockout
Delta-T limit
degrees
-40 °C - 130 °C (-40 °F - 266
°F)
Outlet T-rise
limit enable‘
Enabled
Disabled
Outlet T-rise
degrees
-40 °C - 130 °C (-40 °F - 266
°F)
Outlet T-rise
delay
0-600 seconds
Table 42. Configurable Parameters. (Continued)