ProtoNode Gateway
750-426 69
Modbus Comm Error: F2-2 BI 96 DI 96 10096 nvoMdCmErF22_XXX SNVT_switch
Firing Rate AI 5 AI 5 30009 nvoFirRat_XXX SNVT_lev_percent
Set Point - Steam Pres/ Water Temp AI 7 AI 7 30013 nvoSPStPrWtT_XXX SNVT_count_f
Water Level AI 8 AI 8 30015 nvoWtrLvl_XXX SNVT_press_f
Steam Pres or HW Temp AI 9 AI 9 30017 nvoStPrHWTp_XXX SNVT_count_f
Stack Temp Before Econ AI 11 AI 11 30021 nvoStkTpBfEc_XXX SNVT_temp_p
Water Temp Shell/ Outdoor Temp AI 13 AI 13 30025 nvoWtTpShl_XXX SNVT_temp_p
Boiler Off Point AI 24 AI 24 30047 nvoBlrOffPt_XXX SNVT_count_f
Boiler On Point AI 25 AI 25 30049 nvoBlrOnPt_XXX SNVT_count_f
Fuel 1 Type AI 33 AI 33 30056 nvoFl1Type_XXX SNVT_count_f
Fuel 2 Type AI 34 AI 34 30057 nvoFl2Type_XXX SNVT_count_f
Elapsed Time (First 16 Bits) AI 37 AI 37 30060 nvoElpTm1_XXX SNVT_time_hour
Elapsed Time (Second 16 Bits) AI 38 AI 38 30061 nvoElpTm2_XXX SNVT_time_hour
Number Of Cycles (First 16 Bits) AI 39 AI 39 30062 nvoNumCyc1_XXX SNVT_count_f
Number Of Cycles (Second 16 Bits) AI 40 AI 40 30063 nvoNumCyc2_XXX SNVT_count_f
Elapsed Time AI 43 AI 43 30064 nvoElapTim_XXX SNVT_time_hour
Number Of Cycles AI 44 AI 44 30066 nvoNumCyc_XXX SNVT_count_f
Hawk 2000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued)
RER LER
Point Name
BACnet
Data
Type
BACnet
Object Id
N2
Data
Type
N2 Point
Address
Modbus
Register
Lon Name Lon SNVT Type