ProtoNode Gateway
76 750-426
Bad Ql- Drum Level (06:01) BI 50 DI 50 10050 nvoBdDrumLvl_XXX SNVT_switch
Bad Ql- Stack Temp (06:02) BI 51 DI 51 10051 nvoBdStkTmp_XXX SNVT_switch
Bad Ql- Remote Modulation (06:03) BI 52 DI 52 10052 nvoBdRemMod_XXX SNVT_switch
Bad Ql- Steam Flo (06:04) BI 53 DI 53 10053 nvoBdStmFlo_XXX SNVT_switch
Bad Ql- Mud Drm Shell Tmp (06:05) BI 54 DI 54 10054 nvoBdMdDrSTp_XXX SNVT_switch
Bad Ql- Act5 (VSD) FB (06:06) BI 55 DI 55 10055 nvoBAc5VSDFB_XXX SNVT_switch
Bad Ql- Flue Gas O2 (06:07) BI 56 DI 56 10056 nvoBdFluGsO2_XXX SNVT_switch
Bad Ql- F1 Flo or Usr Def (07:00) BI 57 DI 57 10057 nvoBdF1FlUDf_XXX SNVT_switch
Bad Ql- F2 Flo or Usr Def (07:01) BI 58 DI 58 10058 nvoBdF2FlUDf_XXX SNVT_switch
Bad Ql- Stack Draft or Usr Def (07:02) BI 59 DI 59 10059 nvoBdStDrUDf_XXX SNVT_switch
Bad Ql- Feedwtr Flo or Usr Def (07:03) BI 60 DI 60 10060 nvoBFdWFlUDf_XXX SNVT_switch
Bad Ql- Ecn Out FG Tmp -Usr Def (07:04 BI 61 DI 61 10061 nvoBEcOtFGTp_XXX SNVT_switch
Bad Ql- Ecn In FW Tmp - Usr Def (07:05 BI 62 DI 62 10062 nvoBEcInFWTp_XXX SNVT_switch
Bad Ql- Ecn Out FW Tmp -Usr Def (07:06 BI 63 DI 63 10063 nvoBdcOtFWTp_XXX SNVT_switch
Bad Ql- Air Flo or Usr Def (07:07) BI 64 DI 64 10064 nvoBArFlUsDf_XXX SNVT_switch
Bad Ql- Actuator1 (Air) FB (09:00) BI 65 DI 65 10065 nvoBdAc1ArFB_XXX SNVT_switch
Bad Ql- Actuator2 (F1) FB (09:01) BI 66 DI 66 10066 nvoBdAc2F1FB_XXX SNVT_switch
Bad Ql- Actuator3 (F2) FB (09:02) BI 67 DI 67 10067 nvoBdAc3F2FB_XXX SNVT_switch
Bad Ql- Actuator (FGR) FB (09:03) BI 68 DI 68 10068 nvoBdAcFGRFB_XXX SNVT_switch
Bad Ql- Actuator8 (2nd Air) FB (09:04) BI 69 DI 69 10069 nvoBAc82ArFB_XXX SNVT_switch
Bad Ql- Actuator9 (2nd F1) FB (09:05) BI 70 DI 70 10070 nvoBAc92F1FB_XXX SNVT_switch
Bad Ql- Reserved (09:06) BI 71 DI 71 10071 nvoBdQl09_06_XXX SNVT_switch
Bad Ql- Reserved (09:07) BI 72 DI 72 10072 nvoBdQl09_07_XXX SNVT_switch
HAlm - Steam Press (Xmtr) BI 73 DI 73 10073 nvoHAl_StPrs_XXX SNVT_switch
HAlm - Drum Level (xmtr) BI 74 DI 74 10074 nvoHAl_DrLvl_XXX SNVT_switch
HAlm - Stack Temp (Xmtr) BI 75 DI 75 10075 nvoHAl_StTmp_XXX SNVT_switch
HAlm - Remote Modulation Input BI 76 DI 76 10076 nvoHAlRmMdIn_XXX SNVT_switch
HAlm - Steam Flo (Xmtr) BI 77 DI 77 10077 nvoHAl_StFlo_XXX SNVT_switch
HAlm - Mud Drum Shell Temp (Xmtr) BI 78 DI 78 10078 nvoHAlMdDShT_XXX SNVT_switch
HAlm - VSD Speed Feedback (Xmtr) BI 79 DI 79 10079 nvoHAlVSDSFd_XXX SNVT_switch
HAlm - Flue Gas O2 (Xmtr) BI 80 DI 80 10080 nvoHAlFlGsO2_XXX SNVT_switch
HAlm - F1 Flo (Xmtr) BI 81 DI 81 10081 nvoHAl_F1Flo_XXX SNVT_switch
HAlm - F2 Flo (Xmtr) BI 82 DI 82 10082 nvoHAl_F2Flo_XXX SNVT_switch
HAlm - Stack Draft (Xmtr) BI 83 DI 83 10083 nvoHAlStkDrt_XXX SNVT_switch
HAlm - Feedwater Flo (Xmtr) BI 84 DI 84 10084 nvoHAlFdWtFl_XXX SNVT_switch
HAlm - Econ Outlet FG Temp (Xmtr) BI 85 DI 85 10085 nvoHAlEcOtGT_XXX SNVT_switch
HAlm - Econ Inlet FW Temp (Xmtr) BI 86 DI 86 10086 nvoHAlEcIFWT_XXX SNVT_switch
HAlm - Econ Outlet FW Temp (Xmtr) BI 87 DI 87 10087 nvoHAlEcOFWT_XXX SNVT_switch
HAlm - Air Flo Hi (Xmtr) BI 88 DI 88 10088 nvoHAlArFlHi_XXX SNVT_switch
HHAlm - Stack Tmp Hi-Hi SHUTDWN (Xmtr) BI 89 DI 89 10089 nvoStkTpShdn_XXX SNVT_switch
HAlm - Hi Water Cutoff (Contact) BI 90 DI 90 10090 nvo_HiWtCtof_XXX SNVT_switch
HAlm - Hi Gas Pressure (Contact) BI 91 DI 91 10091 nvo_HiGsPrs_XXX SNVT_switch
HAlm - Hi Oil Temp (Contact) BI 92 DI 92 10092 nvo_HiOilTmp_XXX SNVT_switch
HAlm - Hi Oil Pressure (Contact) BI 93 DI 93 10093 nvo_HiOilPrs_XXX SNVT_switch
HAlm - Hi Water Alm (Contact) BI 94 DI 94 10094 nvo_HiWtrAl_XXX SNVT_switch
HHAlm - Hi-Hi Furn Press SHTDWN BI 95 DI 95 10095 nvoHiFrPrShd_XXX SNVT_switch
Reserved BI 96 DI 96 10096 nvoAB5_15_XXX SNVT_switch
LAlm - Steam Press (Xmtr) BI 97 DI 97 10097 nvoLAl_StPrs_XXX SNVT_switch
LAlm - Drum Level (Xmtr) BI 98 DI 98 10098 nvoLAl_DrLvl_XXX SNVT_switch
LAlm - Stack Temp (Xmtr) BI 99 DI 99 10099 nvoLAl_StTmp_XXX SNVT_switch
Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued)
RER LER
Point Name
BACnet
Data Type
BACnet
Object Id
N2
Data
Type
N2 Point
Address
Modbus
Register
Lon Name Lon SNVT Type