Page 24
Option 5 2 second pulse to output #1 on arming or disarming - This option will map a 2 second pulse to
Output #1 each time Area "A" is armed or disarmed as defined at P531E options 6&7.
Option 6 Day zone alarms (Chime) to output #1 - The option will map alarms from Area "A" zones defined as
Day Zones to output #1. Zones are defined as Day Zones at P411E-P420E option 8 and P421E-P430E
option 4. Day zones are those which normally operate only during periods when the Area is disarmed
and are used as door bells and shop minders etc.
Note: P512E through P518E are as above but apply to outputs 2-8 for Area A
Note: P612E through P618E are as above but apply to outputs 2-8 for Area B
Note: P712E through P718E are as above but apply to outputs 2-8 for Area C
Note: P812E through P818E are as above but apply to outputs 2-8 for Area D
AREA "A" SECONDARY AREA OUTPUT OPTIONS - P521E - P528E
AREA "B" SECONDARY AREA OUTPUT OPTIONS - P621E - P628E
AREA "C" SECONDARY AREA OUTPUT OPTIONS - P721E - P728E
AREA "D" SECONDARY AREA OUTPUT OPTIONS - P821E - P828E
The addresses above allow a number of secondary Area based options to be assigned to any of the 8 outputs.
Address P521 relates to Output 1 options for Area A, address P621 relates to Output 1 options for Area B, address
P721 relates to Output 1 options for Area C and P821 relates to Output 1 options for Area D.
P521E 1E = Any Bypass to output #1
2E = Auto-Bypass warning to output #1
3E = Entry beeps to output #1
4E = Exit beeps to output #1
5E = Arm indication to output #1
6E = Stay Mode Arm indication to output #1
7E = Disarm indication to output #1
8E = Spare
Option 1 Any Bypass to output #1 - This option will produce a change of state at output #1 if any zones are
bypassed, either manually or automatically. This change of state will occur at the end of the Exit delay.
The output reset time (P761E) should be set to zero when this option is enabled.
Option 2 Auto-Bypass warning to output #1 - This option will produce a 2 second pulse at output #1 at the end
of the exit period if a zone has been Auto-Bypassed in Area "A". An Auto-Bypass occurs when a zone is
left un-sealed at the end of the exit delay. At the end of the exit delay zones not defined as Auto-Bypass
which are left un-sealed will produce an activation. Auto-Bypass assignments are found at P411E-
P420E option 7.
Option 3 Entry beeps to output #1 - This option will map the keypad entry beeps to output #1.
Option 4 Exit beeps to output #1 - This option will map the keypad exit beeps to output #1.
Option 5 Arm indication to output #1 - This option will turn output #1 on when Area "A" is armed and turn output
#1 off when Area "A" is disarmed. This change of state occurs at the start of the exit delay and when the
Area is disarmed. Output reset time should be set to zero (P761E0E)
Option 6 Stay Mode Arm indication to output 1 - This option will turn output #1 on when Area "A" is placed in
Stay Mode and turn output #1 off when Area "A" Stay Mode is turned off. Like option 5 this change of
state occurs either at the start of the exit delay or when the Area is disarmed. Output reset time should
be set to zero (P761E0E)
Option 7 Disarm indication to output #1 - This option will turn output #1 on when Area "A" is disarmed either
from Full Arm or Stay Mode and turn output #1 off when Area "A" is Armed or in Stay Mode. Like option
5 this change of state occurs either at the start of the exit delay or when the Area is disarmed. Output
reset time should be set to zero (P761E0E)
Note: P522E through P528E are as above but apply to outputs 2-8 for Area A
Note: P622E through P628E are as above but apply to outputs 2-8 for Area B
Note: P722E through P728E are as above but apply to outputs 2-8 for Area C
Note: P822E through P828E are as above but apply to outputs 2-8 for Area D